SV Quality
The quality values of the transmitted signal in the SV message.
blockType: SubSystem
Path in the library:
|
Description
Block SV Quality It is used to generate the quality value of the transmitted signal in the SV message.
Entrance
# Validity — quality attribute
+
scalar
Details
A quality attribute. Acceptable values from 0 before 3, where:
-
0– no malfunctions detected,Good. -
1– the information received is incorrect and cannot be used.,Invalid. -
2– reserved, not in use,Reserved. -
3– problems with the server, however, the transmitted information may remain relevant,Questionable.
Dependencies
To use this port, check the box Enable external inputs.
# Overflow — ID of the lack of correct representation of the corresponding data values
+
scalar
Details
ID of the absence of a correct representation of the corresponding data values. The considered identifier is applicable only for measurements.
Dependencies
To use this port, check the box Enable external inputs.
# Out of range is the identifier of exceeding the measured value of a predefined acceptable range of values
+
scalar
Details
ID of the value exceeding the measured value of a predefined acceptable range of values. The considered identifier is applicable only for measurements.
Dependencies
To use this port, check the box Enable external inputs.
# Bad reference — Device calibration loss identifier
+
scalar
Details
ID of the device calibration loss. The considered identifier is applicable only for measurements.
Dependencies
To use this port, check the box Enable external inputs.
# Oscillatory — ID of the bounce fixation
+
scalar
Details
The ID of the clatter fixation is used to prevent excessive overload of data transmission channels.
Dependencies
To use this port, check the box Enable external inputs.
# Failure — ID for detecting an internal or external fault
+
scalar
Details
ID of the device’s self-diagnostic system detecting an internal or external malfunction.
Dependencies
To use this port, check the box Enable external inputs.
# Old data — ID of the missing data update
+
scalar
Details
ID of the absence of an update of the relevant data for a certain time.
Dependencies
To use this port, check the box Enable external inputs.
# Inconsistent — identifier of the detection of data inconsistency by the device self-diagnosis system
+
scalar
Details
ID of the detection by the device’s self-diagnostic system of data inconsistency with reality.
Dependencies
To use this port, check the box Enable external inputs.
# Inaccurate — ID of the discrepancy between the data values of the required accuracy
+
scalar
Details
ID of the discrepancy between the data values of the required accuracy. Dependencies
To use this port, check the box Enable external inputs.
# Source is an attribute that provides information about the data source
+
scalar
Details
An attribute that provides information about the data source. The data value can be true, originating from the primary process, or calculated based on the data of the primary process, and set by the user (substituted). Dependencies
To use this port, check the box Enable external inputs.
# Test — ID of the device being in test mode
+
scalar
Details
ID of the device location in testing mode.
Dependencies
To use this port, check the box Enable external inputs.
# Operator blocked — ID for blocking data updates by the operator
+
scalar
Details
ID for blocking data updates by the operator.
Dependencies
To use this port, check the box Enable external inputs.
# Derived is an identifier that determines whether the data is calculated or measured
+
scalar
Details
An identifier that determines whether the data is calculated or measured.
Dependencies
To use this port, check the box Enable external inputs.
Output
#
Quality
—
the value of the quality parameter
scalar | vector
Details
The value of the quality parameter. If the parameter Output size set to equal 4, then this output can be directly connected to the input ports Quality of Currents or Quality of volts of the block SV TX.
| Data types |
|
| Complex numbers support |
No |
Parameters
Main
# Enable external inputs — external quality attribute management option
Details
If this option is selected, the quality attributes can be set via the input ports of the block.
If this option is unchecked, the quality attributes are set in the parameters.
| Default value |
|
| Program usage name |
|
| Evaluatable |
Yes |
# Output size — output size
Details
The size of the output. If the value of this parameter is greater 1, then the output of Quality will become vector, where all the elements match. Maximum value 8.
| Default value |
|
| Program usage name |
|
| Evaluatable |
Yes |
Quality
# Validity — quality attribute
Details
A quality attribute. Acceptable values from 0 before 3, where:
-
0– no malfunctions detected,Good. -
1– the information received is incorrect and cannot be used.,Invalid. -
2– reserved, not in use,Reserved. -
3– problems with the server, however, the transmitted information may remain relevant,Questionable.
Dependencies
To use this option, uncheck the box. Enable external inputs.
| Default value |
|
| Program usage name |
|
| Evaluatable |
Yes |
# Overflow — ID of the absence of a correct representation of the corresponding data values
Details
ID of the absence of a correct representation of the corresponding data values. The considered identifier is applicable only for measurements.
Dependencies
To use this option, uncheck the box. Enable external inputs.
| Default value |
|
| Program usage name |
|
| Evaluatable |
Yes |
# Out of range — ID of the value exceeding the measured value of a predefined acceptable range of values
Details
ID of the value exceeding the measured value of a predefined acceptable range of values. The considered identifier is applicable only for measurements.
Dependencies
To use this option, uncheck the box. Enable external inputs.
| Default value |
|
| Program usage name |
|
| Evaluatable |
Yes |
# Bad reference — Device calibration loss ID
Details
ID of the device calibration loss. The considered identifier is applicable only for measurements.
Dependencies
To use this option, uncheck the box. Enable external inputs.
| Default value |
|
| Program usage name |
|
| Evaluatable |
Yes |
# Oscillatory — ID of the bounce commit
Details
The ID of the clatter fixation is used to prevent excessive overload of data transmission channels.
Dependencies
To use this option, uncheck the box. Enable external inputs.
| Default value |
|
| Program usage name |
|
| Evaluatable |
Yes |
# Failure — ID for detecting an internal or external fault
Details
ID of the device’s self-diagnostic system detecting an internal or external malfunction.
Dependencies
To use this option, uncheck the box. Enable external inputs.
| Default value |
|
| Program usage name |
|
| Evaluatable |
Yes |
# Old data — ID of the missing data update
Details
ID of the absence of an update of the relevant data for a certain time.
Dependencies
To use this option, uncheck the box. Enable external inputs.
| Default value |
|
| Program usage name |
|
| Evaluatable |
Yes |
# Inconsistent — ID of the device’s self-diagnostic system detecting data inconsistencies with reality
Details
ID of the detection by the device’s self-diagnostic system of data inconsistency with reality.
Dependencies
To use this option, uncheck the box. Enable external inputs.
| Default value |
|
| Program usage name |
|
| Evaluatable |
Yes |
# Inaccurate — ID of the discrepancy between the data values of the required accuracy
Details
ID of the discrepancy between the data values of the required accuracy.
Dependencies
To use this option, uncheck the box. Enable external inputs.
| Default value |
|
| Program usage name |
|
| Evaluatable |
Yes |
# Source — an attribute that provides information about the data source
Details
An attribute that provides information about the data source. The data value can be true, originating from the primary process, or calculated based on the data of the primary process, and set by the user (substituted).
Dependencies
To use this option, uncheck the box. Enable external inputs.
| Default value |
|
| Program usage name |
|
| Evaluatable |
Yes |
# Test — ID of the device location in testing mode
Details
ID of the device location in testing mode.
Dependencies
To use this option, uncheck the box. Enable external inputs.
| Default value |
|
| Program usage name |
|
| Evaluatable |
Yes |
# Operator blocked — ID for blocking data updates by the operator
Details
ID for blocking data updates by the operator.
Dependencies
To use this option, uncheck the box. Enable external inputs.
| Default value |
|
| Program usage name |
|
| Evaluatable |
Yes |
# Derived — an identifier that determines whether the data is calculated or measured
Details
An identifier that determines whether the data is calculated or measured.
Dependencies
To use this option, uncheck the box. Enable external inputs.
| Default value |
|
| Program usage name |
|
| Evaluatable |
Yes |
Sample time
# Sample time, s — calculation step
Details
The calculation step is in seconds.
To inherit the calculation step, set this parameter to -1.
| Default value |
|
| Program usage name |
|
| Evaluatable |
Yes |