Engee documentation

High-Frequency Exciter

Electromachine high-frequency excitation.

high frequency exciter

Description

Unit High-Frequency Exciter is an electro-machine high-frequency excitation, the exciter output voltage depends on its rotational speed, and the exciter shaft is connected to the generator shaft.

The unit High-Frequency Exciter can be used as an exciter in a synchronous generator model with a control system, which is shown in the diagram.

self excited exciter 2

The mathematical model High-Frequency Exciter is presented in the diagram.

high frequency exciter 1

In the diagram below

  • - is the equivalent time constant of the exciter;

  • - output voltage of the automatic excitation regulator;

  • - excitation voltage;

  • - generator rotor speed in relative units.

Ports

Input

# Vr — input voltage value from the excitation regulator
scalar

Details

Input voltage value from the excitation regulator in relative units.

Data types

Float64.

Complex numbers support

No

# ω — input value of generator rotor speed
scalar

Details

The input value of the generator rotor speed in relative units.

Data types

Float64.

Complex numbers support

No

Output

# Efd — excitation voltage output
scalar

Details

The output value of the excitation voltage applied to the excitation circuit of a synchronous machine, in relative units.

Data types

Float64.

Complex numbers support

No

Parameters

Main

# Exciter field time constant T_e, s — exciter time constant

Details

Exciter time constant, in seconds.

Usually the exciter time constant value for the electric machine excitation system is 0.3-0.5 s, for thyristor excitation system - 0.02-0.04 s.

Default value

0.5

Program usage name

T_e

Evaluatable

Yes

# Maximum exciter voltage output Efdmax, pu — maximum output value of the excitation voltage

Details

The maximum output value of the excitation voltage applied to the field circuit of a synchronous machine, in relative units.

Default value

2.0

Program usage name

E_fd_max

Evaluatable

Yes

Initial Values

# Initial field voltage Efd0, pu — initial value of excitation voltage

Details

Initial value of the excitation voltage in relative units.

Default value

1.0

Program usage name

E_fd_start

Evaluatable

Yes

Literature

  1. A.A. Yurganov, V.A. Kozhevnikov. Regulation of Excitation of Synchronous Generators.

  2. V.P. Shoiko. Automatic regulation in electrical systems.

Additional options

C code generation: Yes