Bergeron Line (Three-Phase)
A three-phase Bergeron line modeled in Clark coordinates and parameterized by the values of the forward and zero sequences.
blockType: SubSystem
Path in the library:
|
Description
Block Bergeron Line (Three-Phase) simulates a three-phase power transmission line using the traveling wave method, taking into account the finite propagation time of an electromagnetic wave between the ends of the line. The line is modeled in Clark coordinates and is set by the length and linear parameters of the forward and zero sequences.
In contrast to the focused RLC model, Bergeron Line (Three-Phase) It takes into account the propagation delay between the ends of the line, which makes it possible to reproduce the dynamics of extended lines and the associated electromagnetic transients.
A specialized block is used to divide the power system model into parallel computing segments. Connector Bergeron Line (Three-Phase).
Ports
Conserving
#
~1
—
three-phase port
electricity
Details
Three-phase electrical port for connecting the first end of the line to the electrical network.
| Program usage name |
|
#
~2
—
three-phase port
electricity
Details
Three-phase electrical port for connecting the second end of the line to the electrical network.
| Program usage name |
|
Parameters
Main group
# Length, km — length of the power transmission line
Details
The length of the power transmission line.
| Default value |
|
| Program usage name |
|
| Evaluatable |
Yes |
# Positive-sequence resistance, Ohm/km — active linear resistance of the forward sequence
Details
Active linear resistance of the forward sequence.
| Default value |
|
| Program usage name |
|
| Evaluatable |
Yes |
# Zero-sequence resistance, Ohm/km — active linear resistance of the zero sequence
Details
Active linear resistance of the zero sequence.
| Default value |
|
| Program usage name |
|
| Evaluatable |
Yes |
# Positive-sequence inductance, H/km — specific inductance of the direct sequence
Details
The specific inductance of the direct sequence.
| Default value |
|
| Program usage name |
|
| Evaluatable |
Yes |
# Zero-sequence inductance, H/km — specific inductance of the zero sequence
Details
The specific inductance of the zero sequence.
| Default value |
|
| Program usage name |
|
| Evaluatable |
Yes |
# Positive-sequence capacitance, F/km — specific capacity of the direct sequence
Details
The specific capacity of the direct sequence. This value must be greater than zero.
| Default value |
|
| Program usage name |
|
| Evaluatable |
Yes |
# Zero-sequence capacitance, F/km — specific capacity of the zero sequence
Details
The specific capacity of the zero sequence. This value must be greater than zero.
| Default value |
|
| Program usage name |
|
| Evaluatable |
Yes |
Sample time
# Sample time, s — sampling period
Details
Specify the sampling period of the block in seconds.
| Default value |
|
| Program usage name |
|
| Evaluatable |
Yes |