Engee documentation

Three-Winding Autotransformer

Two- or three-winding transformer or autotransformer with customisable winding connections and core type.

Two-Winding Transformer Inductance Matrix Type

two winding transformer inductance matrix type

Two-Winding Autotransformer

two winding autotransformer

Three-Winding Transformer Inductance Matrix Type

three winding transformer inductance matrix type

Three-Winding Autotransformer

three winding autotransformer

Description

The block icon and the transformer configuration change depending on the value of the parameters.

The block allows you to represent one of four models:

  • Two-Winding Transformer Inductance Matrix Type if the Number of windings parameter is set to Two and the Connect windings 1 and 2 in autotransformer is unchecked.

  • Two-Winding Autotransformer Two-Winding Autotransformer if the Number of windings parameter is set to Two and the Connect windings 1 and 2 in autotransformer checkbox is unchecked.

  • Three-winding transformer Three-Winding Transformer Inductance Matrix Type if the Number of windings parameter is set to Three and the Connect windings 1 and 2 in autotransformer checkbox is unchecked.

  • Three winding autotransformer Three-Winding Autotransformer*If the *Number of windings parameter is set to `Three' and the Connect windings 1 and 2 in autotransformer check box is selected.

Models

Model Two-Winding Transformer Inductance Matrix Type

The Two-Winding Transformer Inductance Matrix Type is a three-phase transformer with two windings per phase. Unlike other three-phase transformer models, which are represented by three separate single-phase transformers, this model takes into account the connections between the windings of the different phases. The core and windings of the transformer are shown in the following figure.

two winding transformer inductance matrix type 1

The phase windings of the transformer are numbered as follows:

  • 1 and 2 on phase A.

  • 2 and 5 on phase B.

  • 3 and 6 on phase C.

This type of core implies that phase winding 1 is connected to all other phase windings (2 to 6), whereas in a unit Three-Phase Transformer (Two Windings) (three-phase transformer with three independent cores), winding 1 is connected only to winding 4.

The numbers of phase windings 1 and 2 should not be confused with the numbers used to designate the three-phase windings of a transformer. The three-phase primary winding consists of phase windings 1,2,3 and the three-phase secondary winding consists of phase windings 4,5,6.

The Two-Winding Transformer Inductance Matrix Type model realises the following matrix relationship:

,

where

  • - matrix of winding active resistances;

  • - matrix of inductances;

  • - instantaneous voltages of the windings. Depending on the selected connection group, these are phase or line voltages;

  • - instantaneous currents flowing through the winding. Depending on the selected winding connection group, these are phase or line currents.

Eigen and mutual terms of the inductance matrix are calculated from the ratio of voltages, inductive component of no-load currents and short-circuit reactances at rated frequency. Two sets of values in the forward and zero sequence allow the calculation of 6 diagonal terms and 15 non-diagonal terms of the symmetrical inductance matrix.

The inductance matrix terms (6x6) are calculated from the no-load currents (one three-phase winding excited and the other three-phase winding open) and the forward and zero-sequence short-circuit reactances and , measured with the excited three-phase primary winding and the short-circuit of the three-phase secondary winding.

Let’s assume the following parameters of the direct sequence:

  • - three-phase reactive power absorbed by the primary winding at no-load when the primary winding is excited by the direct sequence voltage when the secondary winding is open.

  • - three-phase reactive power absorbed by the secondary winding at no-load when the secondary winding is excited by the direct sequence voltage when the primary winding is open.

  • - reactive impedance of the direct sequence short circuit observed on the primary side when the secondary winding is short-circuited.

  • , - nominal line voltages of primary and secondary windings.

The intrinsic and mutual reactive resistances of the direct sequence are determined by the expressions:

,

,

.

The intrinsic reactive resistances , and mutual reactive resistances of the zero sequence are determined by usage of similar expressions.

Expansion of the following two (2x2) matrices of direct and zero-sequence reactive resistances

to matrix (6x6) is done by replacing each of the four pairs ] by a submatrix (3x3) of the form:

,

where the eigen and reciprocal terms are defined as

,

.

In order to simulate core losses (active power and forward and zero sequence), additional shunt active resistors are also connected to the leads of one of the three-phase windings.

If the primary winding is selected, the resistors are calculated as:

,

.

The unit takes into account the selected connection type and the unit icon is automatically updated. The input port n1 is added to the block if connection Y with available primary neutral (`Wye with neutral port') is selected. If an available secondary neutral is selected, an additional n2 port will be created.

If the Core type parameters are set to Three single-phase cores, then the model uses three independent circuits with and matrices (3x3). In this case parameters of direct and zero sequence are identical and only direct sequence values are specified.

,

,

.

Model Two-Winding Autotransformer

For an autotransformer, you must specify the same connections for the three-phase primary and secondary windings. If you select the `Wye with neutral port' connection for the primary and secondary windings, the common neutral port `n1' is shown on the left. The figure shows the winding connection of one phase of an autotransformer when both three-phase windings are star-connected (with earthed neutral).

If

two winding autotransformer 1

If

two winding autotransformer 2

W1, W2 windings correspond to the following phase winding numbers:

  • Phase A: W1=1, W2=4.

  • Phase B: W1=2, W2=5.

  • Phase C: W1=3, W2=6.

Model Three-Winding Transformer Inductance Matrix Type

The Three-Winding Transformer Inductance Matrix Type model is a three-phase transformer with three windings per phase. Unlike other three-phase transformer models, which are represented by three separate single-phase transformers, this model takes into account the connections between the windings of the different phases. The core and windings of the transformer are shown in the following figure.

three winding transformer inductance matrix type 1

The phase windings of the transformer are numbered as follows:

  • 1, 4 and 7 on phase A.

  • 2, 5 and 8 on phase B.

  • 3, 6 and 9 on phase C.

This type of core implies that phase winding 1 is connected to all other phase windings (2 to 9).

The numbers of phase windings 1, 2 and 3 should not be confused with the numbers used to designate the three-phase windings of a transformer. The three-phase primary winding consists of phase windings 1,2,3, the three-phase secondary winding consists of phase windings 4,5,6 and the three-phase tertiary winding consists of phase windings 7,8,9.

The Three-Winding Transformer Inductance Matrix Type model realises the following matrix relationship:

,

where

  • - matrix of winding active resistances;

  • - matrix of inductances;

  • - instantaneous voltages of the windings. Depending on the selected connection group, these are phase or line voltages;

  • - instantaneous currents flowing through the winding. Depending on the selected winding connection group, these are phase or line currents.

Eigen and mutual terms of the inductance matrix are calculated from the ratio of voltages, inductive component of no-load currents and short-circuit reactances at rated frequency. Two sets of forward and zero-sequence values allow the calculation of 9 diagonal terms and 36 non-diagonal terms of the symmetric inductance matrix.

The inductance matrix terms (9x9) are calculated from the no-load currents (one three-phase winding excited and the other two three-phase windings open) and short-circuit reactances.

Short-circuit reactances:

and are the reactive resistances of the direct and zero sequences when the three-phase primary winding is excited and the three-phase secondary winding is short-circuited.

and - reactive resistances of direct and zero sequences at excited three-phase primary winding and short circuit of three-phase tertiary winding.

and - reactive resistances of direct and zero sequences at excited three-phase secondary winding and short circuit of three-phase tertiary winding.

Let’s assume the following parameters of direct sequence for three-phase windings and ( and have values 1, 2 or 3):

  • - three-phase reactive power absorbed by the winding at idle when the winding is excited by the direct sequence voltage when the winding is open .

  • - Three-phase reactive power absorbed by the winding at idle running when the winding is excited by the direct sequence voltage when the winding is open .

  • - forward sequence short-circuit reactance observed on the winding side when the winding is short-circuited .

  • , - nominal line voltages of windings and .

The own and mutual reactive resistances of the direct sequence are defined by the expressions:

,

,

.

The intrinsic reactive resistances , and mutual reactive resistances of the zero sequence are determined by usage of similar expressions.

Expansion of the following two (3x3) forward and zero-sequence reactive impedance matrices:

,

to the matrix (9x9) is done by replacing each of the four pairs ] by a submatrix (3x3) of the form:

,

where the eigen and reciprocal terms are defined as

,

.

In order to simulate core losses (active power and forward and zero sequence), additional shunt active resistors are also connected to the leads of one of the three-phase windings.

If winding is selected, the resistors are calculated as:

,

.

The block takes into account the selected connection type and the block icon is automatically updated. The n1 port is added to the block if connection Y with available primary neutral (Wye with neutral port) is selected. If an available secondary or tertiary neutral is selected, an additional n2 or n3 port will be created.

If the Core type parameters are set to Three single-phase cores, then the model uses three independent circuits with and matrices (3x3). In this case the parameters of the direct and zero sequence are identical and only the values of the direct sequence are specified.

,

,

.

Model Three-Winding Autotransformer

For an autotransformer, you must specify the same connections for the three-phase primary and secondary windings. If you select the Wye with neutral port connection for the primary and secondary windings, the common neutral port n1 is displayed on the left. The figure shows the single phase winding connection of an autotransformer when the primary and secondary three-phase windings are star-connected (with earthed neutral) and the tertiary three-phase winding is delta-connected.

If

three winding autotransformer 1

If

three winding autotransformer 2

W1, W2, W3 windings correspond to the following phase winding numbers:

  • Phase A: W1=1, W2=4, W3=7.

  • Phase B: W1=2, W2=5, W3=8.

  • Phase C: W1=3, W2=6, W3=9.

General information

Zero sequence no-load current

Often the zero-sequence no-load current of a transformer with a three-bar core is not provided by the manufacturer. If this is the case, the value can be roughly calculated as described below.

The following figure shows a three-core with one three-phase winding. Only phase B is excited, the voltage is measured at phase A and phase C. The flux , generated by phase B, is equally distributed between phase A and phase C, so that the flux /2 flows into rod A and into rod C. Hence, in this particular case, if the dissipation inductance of winding B is zero, the voltage induced on phases A and C will be equal to . In fact, due to the dissipation inductance of the three windings, the average value of the induced voltage coefficient when windings A, B and C are excited in series should be slightly lower than 0.5.

three phase transformer inductance matrix type (two windings) 2

Let’s assume:

- the average value of the three eigenresistances.

- average value of mutual resistance between phases.

- direct sequence resistance of a three-phase winding.

- zero sequence resistance of a three-phase winding.

- no-load current of the direct sequence.

- zero-sequence no-load current.

,

,

,

,

,

,

where is the induced voltage coefficient (just below 0.5).

Hence, the ratio can be obtained relative to :

.

Obviously, cannot be exactly equal to 0.5 because this would result in an infinite zero-sequence current. In addition, when the three windings are excited by zero-sequence voltage, the magnetic flux must short-circuit through the air and tank surrounding the iron core. The high magnetic resistance of the zero-sequence flux path results in high zero-sequence current.

Assume that . A reasonable value of may be 100%. Thus . According to the above equation for we can determine the value of :

.

The zero sequence losses must also be higher than the direct sequence losses due to additional eddy current losses in the tank.

Finally, the magnitude of the zero-sequence excitation current and the magnitude of the zero-sequence losses are not relevant if the transformer has a delta winding, since this winding acts as a short circuit for the zero sequence.

Winding connections

The three-phase windings of a transformer can be connected as follows:

  • Y star (Y).

  • Y star with available neutral (Yn).

  • Y star with earthed neutral (Yg).

  • Triangle-Star (D1), a triangle 30 degrees behind the Y star.

  • Star triangle (D11), triangle 30 degrees ahead of the star.

The designations D1 and D11 refer to a conventional clock face, which assumes that the phase of the star Y reference voltage is at the 12 o’clock position. The reference voltages for connections D1 and D11 are at 1 o’clock (the triangle is 30 degrees behind star Y) and 11 o’clock (the triangle is 30 degrees ahead of star Y) respectively.

For more information on the operating modes of a three-phase system connected in a Delta pattern, see Problem solving for delta connection of transformer windings.

Limitations

These models are not designed for saturation. To simulate saturation, connect the primary winding of a Two-Winding Transformer (Three-Phase) in parallel with the primary winding. Use the same connection (Yg, D1 or D11) and the same resistance for the two windings connected in parallel. Specify the Y or Yg connection for the secondary winding and leave it open-circuited. State the required voltage, power rating and saturation characteristic. The saturation characteristic is obtained when the transformer is excited by direct sequence voltage. If a transformer with three single-phase cores or a five-bar core is modelled, this model produces acceptable saturation currents because the flux remains inside the steel core. For a three rod core, this saturation model still produces acceptable results even though the zero-sequence flow circulates outside the core and returns through the air and transformer tank surrounding the steel core. Because the zero-sequence flux circulates in the air, the magnetic circuit is essentially linear and its magnetic resistance is high (high magnetising currents). These high zero-sequence currents (100% or more of rated current) required to magnetise the air path are already accounted for in the linear model. Connecting the saturating transformer outside the three-bar linear model with the magnetic-current characteristic obtained for the direct sequence produces the currents required to magnetise the steel core. This model gives acceptable results whether the three-bar transformer has a delta-connected winding or not.

Parameters

Configuration

Number of windings - number of windings
Three (by default)| `Two `

The selection of the Number of windings parameters determines the number of windings of the transformer:

  • Three - three windings per phase, select this value for modelling in Three-Winding Transformer Inductance Matrix Type modes, or Three-Winding Autotransformer.

  • Two - two windings per phase, select these values for modelling in Two-Winding Transformer Inductance Matrix Type or Two-Winding Autotransformer modes.

Core type - core type
Three single-phase cores| Three-limb core or five-limb core (by default).

When Three single-phase cores is selected, only the parameters of the direct sequence will be used to calculate the inductance matrix. If `Three-limb core or five-limb core' is selected, both the forward and zero-sequence parameters will be used to calculate the inductance matrix.

Primary winding connection type - primary winding connection type
Wye with floating neutral | Wye with neutral port | Wye with grounded neutral (by default) | Delta 1 o’clock | Delta 11 o’clock.

Selects the connection type for the three-phase primary winding:

  • Wye with floating neutral - Y star.

  • Wye with neutral port - Y star with available neutral.

  • Wye with grounded neutral - Y star with grounded neutral.

  • `Delta 1 o’clock' - triangle star (D1), a triangle 30 degrees behind the Y star.

  • `Delta 11 o’clock' - star triangle (D11), triangle 30 degrees ahead of the star.

*Secondary winding connection type.
Wye with floating neutral | Wye with neutral port | Wye with grounded neutral (by default) | Delta 1 o’clock | Delta 11 o’clock.

Selects the connection type for the three-phase secondary winding:

  • Wye with floating neutral - Y star.

  • Wye with neutral port - Y star with available neutral.

  • Wye with grounded neutral - Y star with grounded neutral.

  • `Delta 1 o’clock' - triangle star (D1), a triangle 30 degrees behind the Y star.

  • `Delta 11 o’clock' - star triangle (D11), triangle 30 degrees ahead of the star.

*Tertiary winding connection type.
Wye with floating neutral | Wye with neutral port | Wye with grounded neutral (by default) | Delta 1 o’clock | Delta 11 o’clock.

Selects the connection type for the three-phase tertiary winding:

  • Wye with floating neutral - Y star.

  • Wye with neutral port - Y star with available neutral.

  • `Wye with grounded neutral' - Y star with grounded neutral.

  • `Delta 1 o’clock' - triangle star (D1), a triangle 30 degrees behind the Y star.

  • `Delta 11 o’clock' - star triangle (D11), triangle 30 degrees ahead of the star.

Dependencies

This parameter is available if the Number of windings parameter is set to Three.

Connect windings 1 and 2 in autotransformer - galvanic coupling of primary and secondary windings (switching on the autotransformer mode)
On| `Off (by default)

Enable for modelling three-phase primary and secondary autotransformer primary and secondary windings (primary and secondary windings connected in series, with additive voltage). By default it is switched off.

Parameters

Rated apparent power - rated apparent power of the transformer
`260e6 A*B (by default)

Rated transformer power in A*B.

Rated electrical frequency - rated frequency of the transformer
`50 Hz (by default).

Nominal frequency in Hz.

Primary rated voltage - primary rated voltage
`315e3 V (by default).

Phase rated voltage of the primary winding in V.

Secondary rated voltage - secondary rated voltage
`120e3 V (By default)

Phase rated secondary voltage in V.

Tertiary rated voltage - Tertiary rated voltage
`43e3 V (By default)

Phase rated tertiary winding voltage in V.

Dependencies

This parameter is available when the Number of windings parameter is set to Three.

Primary winding resistance, pu - resistance for the primary winding
0.005 (By default).

Primary winding resistance in relative units.

Secondary winding resistance, pu - resistance for secondary winding ass:q[<br>] 0.005 (by default)

Resistance for secondary winding in relative units.

Tertiary winding resistance, pu - resistance for tertiary winding
`0.005 (by default).

Tertiary winding resistance in relative units.

Dependencies

This parameter is available when the Number of windings parameter is set to Three.

Positive-sequence no-load excitation current, % - straight-sequence idle current
0.06 (By default).

No-load excitation current as a percentage of the rated current when the nominal positive-sequence voltage is applied to any terminals of the three-phase winding.

Positive-sequence no-load losses - straight-sequence no-load losses
260e6*0.04/100 W (by default).

Sum of core and winding no-load losses, in W, when nominal direct-sequence voltage is applied to any terminals of the three-phase winding.

Positive-sequence short-circuit reactance X_12₁, pu - total direct-sequence short-circuit reactance of primary and secondary windings
0.087 (by default)

X_12₁ is the reactive resistance of the direct sequence short circuit in relative units. X_12₁ is the reactance measured on the primary winding when the secondary winding is short-circuited.

Dependencies

This parameter is available if the Connect windings 1 and 2 in autotransformer checkbox is unchecked.

Positive-sequence short-circuit reactance X_HL₁, pu - total direct-sequence short-circuit reactance of high and medium voltage windings
0.087 (by default)

X_HL₁, pu* is the direct-sequence short-circuit reactance X_HL₁ in relative units. X_HL₁ is the reactance measured on the primary winding when the secondary winding is short-circuited.

Dependencies

This parameter is available when Connect windings 1 and 2 in autotransformer is checked. When the Connect windings 1 and 2 in autotransformer parameters are selected, the short-circuit reactances are labelled as X_HL, X_HT and X_LT, where H, L and T denote the following terminals:

  • H is the high voltage winding (either winding 1 or winding 2),

  • L is the low voltage winding (either winding 1 or winding 2),

  • T - tertiary winding (winding 3).

Positive-sequence short-circuit reactance X_13₁, pu - total direct-sequence short-circuit reactance of primary and tertiary windings
0.166 (by default)

X_13₁ is the reactive resistance of the direct sequence short circuit in relative units. X_13₁ is the reactance measured on the primary winding when the tertiary winding is short-circuited.

Dependencies

This parameter is available if the Number of windings parameter is set to Three and the Connect windings 1 and 2 in autotransformer checkbox is unchecked.

Positive-sequence short-circuit reactance X_HT₁, pu - total short-circuit reactance of high and low voltage windings of direct sequence
0.166 (by default)

X_HT₁, pu* is the reactive short-circuit resistance of the direct sequence X_HT₁ in relative units. X_HT₁ is the reactance measured on the primary winding when the secondary winding is short-circuited.

Dependencies

This parameter is available when the Number of windings parameter is set to Three and the Connect windings 1 and 2 in autotransformer checkbox is selected. When the Connect windings 1 and 2 in autotransformer parameters are selected, the short-circuit reactances are labelled as X_HL, X_HT and X_LT, where H, L and T denote the following terminals:

  • H - high voltage winding (either winding 1 or winding 2),

  • L - low voltage winding (either winding 1 or winding 2),

  • T - tertiary winding (winding 3).

Positive-sequence short-circuit reactance X_23₁, pu - total direct-sequence short-circuit reactance of secondary and tertiary windings
0.067 (by default)

X_23₁, pu* is the direct sequence reactive short-circuit impedance in relative units. X_23₁ is the reactance measured on the secondary winding when the tertiary winding is short-circuited.

Dependencies

This parameter is available if the Number of windings parameter is set to Three and the Connect windings 1 and 2 in autotransformer checkbox is unchecked.

Positive-sequence short-circuit reactance X_LT₁, pu - total short-circuit reactance of direct sequence windings of medium and low voltage windings
0.067 (by default)

X_LT₁ is the reactive short-circuit resistance of the direct sequence windings in relative units. X_LT₁ is the reactance measured on the primary winding when the secondary winding is short-circuited.

Dependencies

This parameter is available when the Number of windings parameter is set to Three and Connect windings 1 and 2 in autotransformer is checked. When the Connect windings 1 and 2 in autotransformer parameters are selected, the short-circuit reactances are labelled as X_HL, X_HT and X_LT, where H, L and T denote the following terminals:

  • H is the high voltage winding (either winding 1 or winding 2),

  • L is the low voltage winding (either winding 1 or winding 2),

  • T - tertiary winding (winding 3).

Zero-sequence no-load excitation current with Delta windings open, % - zero-sequence no-load current when zero-sequence voltage is applied to any of the windings connected in Yg or Yn
100 (By default)

No-load excitation current as a percentage of the rated current when the rated zero sequence voltage is applied to any of the three-phase winding terminals connected to Yg.

If the transformer contains delta connected windings (D1 or D11), the zero sequence current flowing into the winding Yg or Yn connected to the zero sequence voltage source does not represent only the excitation current, since zero sequence currents also flow in the winding. Therefore, it is necessary to specify the no-load zero-sequence circulating current obtained when the delta windings are open.

In order to measure this field current, it is necessary to temporarily change the delta connection of the windings from D1 or D11 to Y, Yg or Yn and connect the field winding to Yg or Yn to provide a short circuit for zero sequence currents.

Zero-sequence no-load losses with delta windings open - zero-sequence no-load losses with delta windings open
260e6*1/100 W (by default)

Sum of core and winding idle losses in W when the rated zero sequence voltage is applied to any group of winding terminals connected to Yg or Yn. The delta winding must be temporarily open-circuited to measure these losses.

If the transformer contains delta-connected windings (D1 or D11), the zero-sequence current flowing into the winding Yg or Yn connected to the zero-sequence voltage source does not represent only the excitation current, since zero-sequence currents also flow in the winding. It is therefore necessary to specify the no-load zero-sequence circulating current obtained when the delta windings are open.

Zero-sequence short-circuit reactance X_12₀, pu - total zero-sequence short-circuit reactance of primary and secondary windings
0.1 (by default)

Zero-sequence short-circuit reactance X_12₀ in relative units. X_12₀ is the reactance measured on the primary winding when the secondary winding is short-circuited.

Dependencies

This parameter is available if the Connect windings 1 and 2 in autotransformer checkbox is unchecked.

Zero-sequence short-circuit reactance X_HL₀, pu - total zero-sequence short-circuit reactance of high and medium voltage windings
0.1 (by default)

Zero-sequence short-circuit reactance X_HL₀ in relative units. X_HL₀ is the reactance measured on the primary winding when the secondary winding is short-circuited.

Dependencies

This parameter is available when Connect windings 1 and 2 in autotransformer is checked. When the Connect windings 1 and 2 in autotransformer parameters are selected, the short-circuit reactances are labelled as X_HL, X_HT and X_LT, where H, L and T denote the following terminals:

  • H is the high voltage winding (either winding 1 or winding 2),

  • L is the low voltage winding (either winding 1 or winding 2),

  • T - tertiary winding (winding 3).

Zero-sequence short-circuit reactance X_13₀, pu - total zero-sequence short-circuit reactance of primary and tertiary windings
0.2 (by default)

Zero-sequence short-circuit reactance X_13₀ in relative units. X_13₀ is the reactance measured on the primary winding when the tertiary winding is short-circuited.

Dependencies

This parameter is available if the Number of windings parameter is set to Three and the Connect windings 1 and 2 in autotransformer checkbox is unchecked.

Zero-sequence short-circuit reactance X_HT₀, pu - total zero-sequence short-circuit reactance of high and low voltage windings
0.2 (by default)

Zero-sequence short-circuit reactance X_HT₀ in relative units. X_HT₀ is the reactance measured on the primary winding when the secondary winding is short-circuited.

Dependencies

This parameter is available when the Number of windings parameter is set to Three and the Connect windings 1 and 2 in autotransformer checkbox is selected. When the Connect windings 1 and 2 in autotransformer parameters are selected, the short-circuit reactances are labelled as X_HL, X_HT and X_LT, where H, L and T denote the following terminals:

  • H is the high voltage winding (either winding 1 or winding 2),

  • L is the low voltage winding (either winding 1 or winding 2),

  • T - tertiary winding (winding 3).

Zero-sequence short-circuit reactance X_23₀, pu - total zero-sequence short-circuit reactance of secondary and tertiary windings
0.3 (by default)

Zero-sequence short-circuit reactance X_23₀ in relative units. X_23₀ is the reactance measured on the secondary winding when the tertiary winding is short-circuited.

Dependencies

This parameter is available if the Number of windings parameter is set to Three and the Connect windings 1 and 2 in autotransformer checkbox is unchecked.

Zero-sequence short-circuit reactance X_LT₀, pu - total zero-sequence short-circuit reactance of medium and low voltage windings
0.3 (by default)

Zero-sequence short-circuit reactance X_LT₀ in relative units. X_LT₀ is the reactance measured on the primary winding when the secondary winding is short-circuited.

Dependencies

This parameter is available when the Number of windings parameter is set to Three and Connect windings 1 and 2 in autotransformer is checked. When the Connect windings 1 and 2 in autotransformer parameters are selected, the short-circuit reactances are labelled as X_HL, X_HT and X_LT, where H, L and T denote the following terminals:

  • H is the high voltage winding (either winding 1 or winding 2),

  • L is the low voltage winding (either winding 1 or winding 2),

  • T - tertiary winding (winding 3).