Voltage Transformer
Page in progress. |
Voltage Transformer (VT).
blockType: AcausalElectricPowerSystems.Passive.Transformers.Voltage
Path in the library:
|
Description
The Voltage Transformer block is a multiwinding transformer that can be modelled as a voltage transformer with different levels of nonlinearity.
The parameters group Initial Conditions is used to set the initial current or flux for each of the inductors, as well as for the load inductors in case the checkbox Include burden. is checked. Note that these values are not used if the Start simulation from steady state checkbox is selected in the solver configuration Solver Configuration.
The group of parameters Parasitic represents small parasitic effects. Small parallel conductances may be required for modelling some circuit topologies.
For more information on the equations and modes implemented in the block see Nonlinear Transformer.
Ports
Conserving
#
1+
—
positive terminal of the first winding
electricity
Details
Electrical port, represents the terminal of the first winding with positive polarity.
Program usage name |
|
#
1-
—
negative terminal of the first winding
electricity
Details
Electrical port, represents the terminal of the first winding with negative polarity.
Program usage name |
|
#
2+
—
positive terminal of the second winding
electricity
Details
Electricity port, represents the terminal of the second winding with positive polarity.
Dependencies
To use this port, uncheck Include burden.
Program usage name |
|
#
2-
—
negative terminal of the second winding
electricity
Details
Electricity port, represents the terminal of the second winding with negative polarity.
Dependencies
To use this port, uncheck Include burden.
Program usage name |
|
#
3+
—
positive terminal of the third winding
electricity
Details
Electricity port, represents the terminal of the third winding with positive polarity.
Dependencies
To use this port, uncheck Include burden, and for the parameters Number of windings value. Three
, Four
, Five
or Six
.
Program usage name |
|
#
3-
—
negative terminal of the third winding
electricity
Details
Electricity port, represents the terminal of the third winding with negative polarity.
Dependencies
To use this port, uncheck Include burden, and for the parameters Number of windings value. Three
, Four
, Five
or Six
.
Program usage name |
|
#
4+
—
positive terminal of the fourth winding
electricity
Details
Electricity port, represents the terminal of the fourth winding with positive polarity.
Dependencies
To use this port, uncheck Include burden, and for the parameters Number of windings value. Four
, Five
or Six
.
Program usage name |
|
#
4-
—
negative terminal of the fourth winding
electricity
Details
Electricity port, represents the terminal of the fourth winding with negative polarity.
Dependencies
To use this port, uncheck Include burden, and for the parameters Number of windings value. Four
, Five
or Six
.
Program usage name |
|
#
5+
—
positive terminal of the fifth winding
electricity
Details
Electricity port, represents the terminal of the fifth winding with positive polarity.
Dependencies
To use this port, uncheck Include burden, and for the parameters Number of windings the value of Five
or Six
.
Program usage name |
|
#
5-
—
negative terminal of the fifth winding
electricity
Details
Electricity port, represents the terminal of the fifth winding with negative polarity.
Dependencies
To use this port, uncheck Include burden, and for the parameters Number of windings the value of Five
or Six
.
Program usage name |
|
#
6+
—
positive terminal of the sixth winding
electricity
Details
Electricity port, represents the terminal of the sixth winding with positive polarity.
Dependencies
To use this port, uncheck Include burden, and for the parameters Number of windings the value of Six
.
Program usage name |
|
#
6-
—
negative terminal of the sixth winding
electricity
Details
Electricity port, represents the terminal of the sixth winding with negative polarity.
Dependencies
To use this port, uncheck Include burden, and for the parameters Number of windings the value of Six
.
Program usage name |
|
Output
#
v2
—
second winding voltage
scalar
Details
Voltage of the second winding.
Dependencies
To use this port, select the checkbox Include burden.
Data types |
|
Complex numbers support |
No |
#
v3
—
voltage of the third winding.
scalar
Details
Voltage of the third winding.
Dependencies
To use this port, select the checkbox Include burden, and set the value for the parameters Number of windings. Three
, Four
, Five
or Six
.
Data types |
|
Complex numbers support |
No |
#
v4
—
fourth winding voltage
scalar
Details
Voltage of the fourth winding.
Dependencies
To use this port, select the checkbox Include burden, and set the value for the parameters Number of windings to . Four
, Five
or Six
.
Data types |
|
Complex numbers support |
No |
#
v5
—
fifth winding voltage
scalar
Details
Voltage of the fifth winding.
Dependencies
To use this port, select the checkbox Include burden, and set the parameters Number of windings to the value of Five
or Six
.
Data types |
|
Complex numbers support |
No |
#
v6
—
sixth winding voltage
scalar
Details
Voltage of the sixth winding.
Dependencies
To use this port, select the checkbox Include burden, and set the parameters Number of windings to a value of Six
.
Data types |
|
Complex numbers support |
No |
Parameters
Main
#
Number of windings —
switching between two-, three-, four-, five- and six-winding transformers
Two
| Three
| Four
| Five
| Six
Details
Switching between two-, three-, four-, five- and six-winding transformers.
-
Two
- the unit simulates a two-winding transformer. -
Three
- The block simulates a three-winding transformer. -
Four
- The block simulates a four-winding transformer. -
Five
- The block simulates a five-winding transformer. -
Six
- The block simulates a six-winding transformer.
Values |
|
Default value |
|
Program usage name |
|
Evaluatable |
No |
#
Turns ratio parameterization by —
option for setting the transformer ratio of the VT
Number of turns
Details
Select one of the following methods for setting the VT ratio:
-
Number of turns
- through the number of turns.
Values |
|
Default value |
|
Program usage name |
|
Evaluatable |
No |
# First winding number of turns — number of turns of the first winding
Details
Number of turns of the first winding wire of the transformer.
Dependencies
To use this parameter, set the parameters Turns ratio parameterization by to . Number of turns
.
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
# Second winding number of turns — number of turns of the second winding
Details
Number of turns of the second winding wire of the transformer.
Dependencies
To use this parameter, set the parameters Turns ratio parameterization by to . Number of turns
.
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
# Third winding number of turns — number of turns of the third winding
Details
Number of turns of the third winding wire of the transformer.
Dependencies
To use this parameter, set the Turns ratio parameterization by parameters to and the parameters to . Number of turns`and set the parameters Number of windings. `Three
, Four
, Five
or Six
.
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
# Fourth winding number of turns — number of turns of the fourth winding
Details
Number of turns of the fourth winding wire of the transformer.
Dependencies
To use this parameter, set the parameters Turns ratio parameterization by to the value of Number of turns`and set the Number of windings parameters to `Four
, Five
or Six
.
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
# Fifth winding number of turns — number of turns of the fifth winding
Details
Number of turns of the fifth winding wire of the transformer.
Dependencies
To use this parameter, set the parameters Turns ratio parameterization by to the value of Number of turns`and set the Number of windings parameters to `Five
or Six
.
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
# Sixth winding number of turns — number of turns of the sixth winding
Details
Number of turns of the sixth winding wire of the transformer.
Dependencies
To use this parameter, set the parameters Turns ratio parameterization by to the value of Number of turns`and set the Number of windings parameters to `Six
.
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Winding parameterized by —
type of winding distribution representation
Combined primary and secondary values
| Separate primary and secondary values
Details
The method of dissipation in the winding. Defined as:
-
Combined primary and secondary values
- use concentrated resistance and inductance values representing the combined leakage in the primary and secondary windings. -
Separate primary and secondary values
- use separate resistances and inductances to represent the leakage in the primary and secondary windings.
Dependencies
To use this parameter, set the parameter Number of windings to Two
.
Values |
|
Default value |
|
Program usage name |
|
Evaluatable |
No |
#
Combined winding resistance —
total active resistance of windings
Ohm
| GOhm
| MOhm
| kOhm
| mOhm
Details
The concentrated equivalent active resistance Req, which represents the combined power losses of the first and second windings.
Dependencies
To use this parameter, set the parameters Winding parameterized by to . Combined primary and secondary values
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Combined leakage inductance —
total scattering inductance
H
| mH
| nH
| uH
Details
The cumulative equivalent inductance Leq, which is the combined magnetic flux losses of the first and second windings.
Dependencies
To use this parameter, set the parameters Winding parameterized by to . Combined primary and secondary values
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
First winding resistance —
active resistance of the first winding
Ohm
| GOhm
| MOhm
| kOhm
| mOhm
Details
The active resistance R1, which represents the power loss of the first winding.
Dependencies
To use this parameter, set the Winding parameterized by parameters to the value of Separate primary and secondary values
or set the Number of windings parameters to . Three
, Four
, Five
or Six
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
First leakage inductance —
dissipation inductance of the first winding
H
| mH
| nH
| uH
Details
The inductance L1, which represents the magnetic flux losses of the first winding.
Dependencies
To use this parameter, set the Winding parameterized by parameters to the value of Separate primary and secondary values
or set the Number of windings parameters to . Three
, Four
, Five
or Six
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Second winding resistance —
active resistance of the second winding
Ohm
| GOhm
| MOhm
| kOhm
| mOhm
Details
The active resistance R2, which represents the power loss of the second winding.
Dependencies
To use this parameter, set the Winding parameterized by parameters to the value of Separate primary and secondary values
or set the Number of windings parameters to . Three
, Four
, Five
or Six
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Second leakage inductance —
dissipation inductance of the second winding
H
| mH
| nH
| uH
Details
The inductance L2, which represents the magnetic flux losses of the second winding.
Dependencies
To use this parameter, set the Winding parameterized by parameters to the value of Separate primary and secondary values
or set the Number of windings parameters to . Three
, Four
, Five
or Six
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Third winding resistance —
active resistance of the third winding
Ohm
| GOhm
| MOhm
| kOhm
| mOhm
Details
The active resistance R3, which represents the power loss of the third winding.
Dependencies
To use this parameter, set the parameter Number of windings to . Three
, Four
, Five
or Six
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Third leakage inductance —
dissipation inductance of the third winding
H
| mH
| nH
| uH
Details
The L3 inductance, which represents the magnetic flux losses of the third winding.
Dependencies
To use this parameter, set the parameter Number of windings to the value of Three
, Four
, Five
or Six
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Fourth winding resistance —
active resistance of the fourth winding
Ohm
| GOhm
| MOhm
| kOhm
| mOhm
Details
The active resistance R4, which represents the power loss of the fourth winding.
Dependencies
To use this parameter, set the parameter Number of windings to . Four
, Five
or Six
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Fourth leakage inductance —
dissipation inductance of the fourth winding
H
| mH
| nH
| uH
Details
The L4 inductance, which represents the magnetic flux losses of the fourth winding.
Dependencies
To use this parameter, set the parameter Number of windings to . Four
, Five
or Six
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Fifth winding resistance —
active resistance of the fifth winding
Ohm
| GOhm
| MOhm
| kOhm
| mOhm
Details
The active resistance R5, which represents the power loss of the fifth winding.
Dependencies
To use this parameter, set the parameters Number of windings to the value of Five
or Six
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Fifth leakage inductance —
dissipation inductance of the fifth winding
H
| mH
| nH
| uH
Details
The L5 inductance, which represents the magnetic flux losses of the fifth winding.
Dependencies
To use this parameter, set the parameters Number of windings to the value of Five
or Six
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Sixth winding resistance —
active resistance of the sixth winding
Ohm
| GOhm
| MOhm
| kOhm
| mOhm
Details
The active resistance R6, which represents the power loss of the sixth winding.
Dependencies
To use this parameter, set the parameter Number of windings to the value of Six
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Sixth leakage inductance —
dissipation inductance of the sixth winding
H
| mH
| nH
| uH
Details
The L6 inductance, which represents the magnetic flux losses of the sixth winding.
Dependencies
To use this parameter, set the parameter Number of windings to the value of Six
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
Magnetization
#
Magnetization resistance —
active magnetising resistance
Ohm
| GOhm
| MOhm
| kOhm
| mOhm
Details
The active resistance Rm representing the magnetic losses in the transformer core.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Magnetization inductance parameterized by —
block parameterization
Single inductance (linear)
| Single saturation point
| Magnetic flux versus current characteristic
| Magnetic flux density versus magnetic field strength characteristic
| Magnetic flux density versus magnetic field strength characteristic with hysteresis
| Voltage versus current characteristic
Details
A method for parameterising a block. Defined as:
-
Single inductance (linear)
- values for the number of turns, unsaturated and saturated inductances, saturation magnetic flux and parasitic parallel conductivity are specified. This option is used by default. -
Single saturation point
- The values for the number of turns, unsaturated inductance and parasitic parallel conductivity are specified. -
Magnetic flux versus current characteristic
- In addition to the number of turns and the value of the parasitic parallel conductance, the current vector and the magnetic flux vector are given to complete the magnetic flux-current table. -
Magnetic flux density versus magnetic field strength characteristic
- In addition to the number of turns and the parasitic parallel conductance value, the effective length and cross-sectional area of the core are given, as well as the magnetic field strength vector and the magnetic induction vector to complete the magnetic induction versus magnetic field strength table. -
Magnetic flux density versus magnetic field strength characteristic with hysteresis
- In addition to the number of turns, effective length and cross-sectional area of the core, the values of the initial derivative of the angysteresis B-H curve, magnetic induction and field strength at a certain point of the B-H curve, as well as the reversible magnetisation coefficient, volume coupling coefficient and interdomain coupling coefficient to determine the magnetic induction as a function of the current value and history of the magnetic field strength are given. -
Voltage versus current characteristic
- setting saturation through the volt-ampere characteristic (VAC).
Values |
|
Default value |
|
Program usage name |
|
Evaluatable |
No |
#
Magnetic field strength vector, H —
vector of magnetic field strength values
A/m
Details
Magnetic field strength values used to fill in the table of dependence of magnetic induction on magnetic field strength.
Dependencies
To use this parameter, set the Magnetization inductance parameterized by parameters to . Magnetic flux versus current characteristic
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Magnetic flux density vector, B —
vector of magnetic induction values
G
| T
Details
Magnetic induction values used to fill in the table of dependence of magnetic induction on magnetic field strength.
Dependencies
To use this parameter, set the Magnetization inductance parameterized by parameters to . Magnetic flux versus current characteristic
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Effective length —
effective core length
m
| cm
| ft
| in
| km
| mi
| mm
| um
| yd
Details
The effective core length, i.e. the average length of the magnetic flux path.
Dependencies
To use this parameter, set the parameters Magnetization inductance parameterized by to Magnetic flux density versus magnetic field strength characteristic
or Magnetic flux density versus magnetic field strength characteristic with hysteresis
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Effective cross-sectional area —
effective cross-sectional area
m^2
| cm^2
| ft^2
| in^2
| km^2
| mi^2
| mm^2
| um^2
| yd^2
Details
The effective cross-sectional area of the core, i.e. the average area of the magnetic flux path.
Dependencies
To use this parameter, set the parameters Magnetization inductance parameterized by to the value of Magnetic flux density versus magnetic field strength characteristic
or Magnetic flux density versus magnetic field strength characteristic with hysteresis
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Unsaturated inductance —
unsaturated inductance
H
| mH
| nH
| uH
Details
The inductance value used when the transformer is operating in the linear region.
Dependencies
To use this parameter, set the parameters Magnetization inductance parameterized by to Single inductance (linear)
or Single saturation point
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Saturated inductance —
saturable inductance
H
| mH
| nH
| uH
Details
The inductance value used when the transformer is operating in the saturation zone.
Dependencies
To use this parameter, set the parameter Magnetization inductance parameterized by to the value of Single saturation point
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Current vector, i —
current vector
A
| MA
| kA
| mA
| nA
| pA
| uA
Details
Current values used to populate the magnetic flux-current table.
Dependencies
To use this parameter, set the Magnetization inductance parameterized by parameters to Magnetic flux versus current characteristic
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Magnetic flux vector, Φ —
vector of magnetic flux values
Wb
| N*m/A
| mN*m/A
Details
Magnetic flux values used to populate the magnetic flux-current table.
Dependencies
To use this parameter, set the parameters Magnetization inductance parameterized by to . Magnetic flux versus current characteristic
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Current vector for V-I option, (secondary side - RMS) —
vector of effective values of current VAC
A
| MA
| kA
| mA
| nA
| pA
| uA
Details
The vector of effective values of the SAC current.
Dependencies
To use this parameter, set the parameter Magnetization inductance parameterized by to . Voltage versus current characteristic
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Voltage vector for V-I option, (secondary side - RMS) —
vector of effective values of voltage VAC
V
| MV
| kV
| mV
Details
The vector of effective values of the VAC voltage.
Dependencies
To use this parameter, set the parameter Magnetization inductance parameterized by to . Voltage versus current characteristic
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
System frequency —
network frequency
Hz
| GHz
| MHz
| kHz
Details
Network frequency.
Dependencies
To use this parameter, set the Magnetization inductance parameterized by parameters to Voltage versus current characteristic
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Saturation magnetic flux —
saturated magnetic flux
Wb
| N*m/A
| mN*m/A
Details
The value of the magnetic flux at which the transformer becomes saturated.
Dependencies
To use this parameter, set the parameters Magnetization inductance parameterized by to . Single saturation point
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Anhysteretic B-H gradient when H is zero —
derivative of the B-H anhysteresis curve near zero field strength
H/m
| mH/m
| nH/m
| uH/m
| H/km
| mH/km
| T*m/A
Details
The derivative of the anhysteresis (no hysteresis) B-H curve near zero field strength. Set as the average of the derivative of the positive and negative hysteresis curves.
Dependencies
To use this parameter, set the parameter Magnetization inductance parameterized by to . Magnetic flux density versus magnetic field strength characteristic with hysteresis
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Flux density point on anhysteretic B-H curve —
value of magnetic induction at the point on the angysteresis curve B-H
G
| T
Details
Specify the value of magnetic induction at a point on the anhysteresis curve. The most accurate option is to select the point at high field strength when the positive and negative hysteresis curves coincide.
Dependencies
To use this parameter, set the parameter Magnetization inductance parameterized by to . Magnetic flux density versus magnetic field strength characteristic with hysteresis
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Corresponding field strength —
corresponding field strength
A/m
Details
Corresponding field strength for the point given by the parameters Flux density point on anhysteretic B-H curve.
Dependencies
To use this parameter, set the Magnetization inductance parameterized by parameters to . Magnetic flux density versus magnetic field strength characteristic with hysteresis
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
# Coefficient for reversible magnetization, c — reversible magnetisation coefficient
Details
The fraction of magnetisation that is reversible. The value must be greater than zero and less than one.
Dependencies
To use this parameter, set the parameter Magnetization inductance parameterized by to the value of Magnetic flux density versus magnetic field strength characteristic with hysteresis
.
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Bulk coupling coefficient, K —
volume coupling coefficient
A/m
Details
A parameter of the Giles-Atherton model that primarily determines the value of field strength at which the B-H curve crosses the line of zero magnetic induction.
Dependencies
To use this parameter, set the parameters Magnetization inductance parameterized by to . Magnetic flux density versus magnetic field strength characteristic with hysteresis
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
# Inter-domain coupling factor, α — interdomain coefficient
Details
A Giles-Atherton parameter affecting primarily the points of intersection of the B-H curves with the zero field strength line. Typical values range from 1e-4
to 1e-3
.
Dependencies
To use this parameter, set the parameter Magnetization inductance parameterized by to the value of Magnetic flux density versus magnetic field strength characteristic with hysteresis
.
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Interpolation option —
interpolation option
Linear
| Smooth
Details
The interpolation option of the lookup table. Defined as:
-
Linear
- select this option to get the best performance. -
Smooth
- select this option to obtain a continuous curve with continuous first order derivatives.
Values |
|
Default value |
|
Program usage name |
|
Evaluatable |
No |
Burden
# Include burden — load of secondary windings of VTs
Details
If this checkbox is selected, an internal load is connected to the secondary windings, the output ports will change from electrical to directional (scalars).
Default value |
|
Program usage name |
|
Evaluatable |
No |
#
Burden type —
load type
R
| L
| Series RL
Details
Load Type:
-
R
- Active. -
L
- inductive. -
Series RL
- series active-inductive.
Dependencies
To use this parameter, select the check box Include burden.
Values |
|
Default value |
|
Program usage name |
|
Evaluatable |
No |
#
Second winding burden resistance —
active load resistance of the second winding
Ohm
| GOhm
| MOhm
| kOhm
| mOhm
Details
The active load resistance of the second winding.
Dependencies
To use this parameter, tick the checkbox Include burden, and for the parameter Burden type set the value to R
or Series RL
;
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Second winding burden inductance —
load inductance of the second winding
H
| mH
| nH
| uH
Details
Load inductance of the second winding.
Dependencies
To use this parameter, tick the checkbox Include burden, and for the parameter Burden type set the value to L
or Series RL
;
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Third winding burden resistance —
active load resistance of the third winding
Ohm
| GOhm
| MOhm
| kOhm
| mOhm
Details
Active load resistance of the third winding.
Dependencies
To use this parameters:
-
select the check box Include burden;
-
set the Burden type parameters to
R
orSeries RL
; -
set the Number of windings parameters to
Three
,Four
,Five
orSix
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Third winding burden inductance —
load inductance of the third winding
H
| mH
| nH
| uH
Details
Load inductance of the third winding.
Dependencies
To use this parameters:
-
select the check box Include burden;
-
set the Burden type parameters to
L
orSeries RL
; -
set the Number of windings parameters to
Three
,Four
,Five
orSix
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Fourth winding burden resistance —
active load resistance of the fourth winding
Ohm
| GOhm
| MOhm
| kOhm
| mOhm
Details
The active load resistance of the fourth winding.
Dependencies
To use this parameters:
-
Select the checkbox Include burden;
-
set the Burden type parameters to
R
orSeries RL
; -
set the Number of windings parameters to
Four
,Five
orSix
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Fourth winding burden inductance —
load inductance of the fourth winding
H
| mH
| nH
| uH
Details
Load inductance of the fourth winding.
Dependencies
To use this parameters:
-
select the check box Include burden;
-
set the Burden type parameters to
L
orSeries RL
; -
set the Number of windings parameters to
Four
,Five
orSix
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Fifth winding burden resistance —
active load resistance of the fifth winding
Ohm
| GOhm
| MOhm
| kOhm
| mOhm
Details
The active load resistance of the fifth winding.
Dependencies
To use this parameters:
-
select the check box Include burden;
-
set the Burden type parameters to
R
orSeries RL
; -
set the Number of windings parameters to
Five
orSix
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Fifth winding burden inductance —
load inductance of the fifth winding
H
| mH
| nH
| uH
Details
The load inductance of the fifth winding.
Dependencies
To use this parameters:
-
select the check box Include burden;
-
set the Burden type parameters to
L
orSeries RL
; -
set the Number of windings parameters to
Five
orSix
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Sixth winding burden resistance —
active load resistance of the sixth winding
Ohm
| GOhm
| MOhm
| kOhm
| mOhm
Details
The active load resistance of the sixth winding.
Dependencies
To use this parameters:
-
select the check box Include burden;
-
set the Burden type parameters to
R
orSeries RL
; -
set the Number of windings parameters to
Six
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Sixth winding burden inductance —
load inductance of the sixth winding
H
| mH
| nH
| uH
Details
Load inductance of the sixth winding.
Dependencies
To use this parameters:
-
select the check box Include burden;
-
set the Burden type parameters to
L
orSeries RL
; -
set the Number of windings parameters to
Six
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
Initial Conditions
#
Combined leakage current —
initial current of the total dissipation inductance
A
| MA
| kA
| mA
| nA
| pA
| uA
Details
Initial value of the total dissipation inductance current.
Dependencies
To use this parameter, set the parameter Winding parameterized by to . Combined primary and secondary values
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
First leakage inductance current —
initial current of the first winding dissipation inductance
A
| MA
| kA
| mA
| nA
| pA
| uA
Details
Initial value of the dissipation inductance current of the first winding of the transformer.
Dependencies
To use this parameter, set the parameters Winding parameterized by to Separate primary and secondary values
or set the parameters Number of windings. Three
, Four
, Five
or Six
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Second leakage inductance current —
initial current of the second winding dissipation inductance
A
| MA
| kA
| mA
| nA
| pA
| uA
Details
Initial value of the dissipation inductance current of the second winding of the transformer.
Dependencies
To use this parameter, set the parameters Winding parameterized by to Separate primary and secondary values
or set the parameters Number of windings. Three
, Four
, Five
or Six
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Third leakage inductance current —
initial current of the third winding dissipation inductance
A
| MA
| kA
| mA
| nA
| pA
| uA
Details
Initial value of the dissipation inductance current of the third winding of the transformer.
Dependencies
To use this parameter, set the parameters Number of windings to . Three
, Four
, Five
or Six
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Fourth leakage inductance current —
initial current of the fourth winding dissipation inductance
A
| MA
| kA
| mA
| nA
| pA
| uA
Details
Initial value of the dissipation inductance current of the fourth winding of the transformer.
Dependencies
To use this parameter, set the parameters Number of windings to . Four
, Five
or Six
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Fifth leakage inductance current —
initial current of the fifth winding dissipation inductance
A
| MA
| kA
| mA
| nA
| pA
| uA
Details
Initial value of the dissipation inductance current of the fifth winding of the transformer.
Dependencies
To use this parameter, set the parameters Number of windings to Five
or Six
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Sixth leakage inductance current —
initial current of the sixth winding dissipation inductance
A
| MA
| kA
| mA
| nA
| pA
| uA
Details
Initial value of the dissipation inductance current of the sixth winding of the transformer.
Dependencies
To use this parameter, set the parameters Number of windings. Six
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Specify magnetization inductance state by —
option for setting the initial state
Current
| Magnetic flux
Details
The option to set the initial state. Defined as:
-
Current
- setting the initial state of the transformer by the initial current through the transformer. This option is used by default. -
Magnetic flux
- setting the initial state of the transformer by magnetic flux.
Dependencies
To use this parameter, set the parameters Magnetization inductance parameterized by to . Magnetic flux density versus magnetic field strength characteristic with hysteresis
.
Values |
|
Default value |
|
Program usage name |
|
Evaluatable |
No |
#
Magnetization inductance current —
initial magnetising inductance current
A
| MA
| kA
| mA
| nA
| pA
| uA
Details
The initial current value used to calculate the magnetic flux value at zero time. This is the current flowing through the magnetising inductance of the transformer. The total magnetising current consists of the current through the active magnetising resistance and the current through the magnetising inductance.
Dependencies
This parameter is only used when selecting the value Current
for the parameter Specify magnetization inductance state by.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Magnetization inductance magnetic flux —
initial magnetic flux of the magnetising inductance
Wb
| N*m/A
| mN*m/A
Details
The value of the magnetic flux at zero time.
Dependencies
This parameter is only used when selecting the value Magnetic flux
for the parameter Specify magnetization inductance state by.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Magnetization inductance magnetic flux density —
initial magnetic induction of the magnetising inductance
G
| T
Details
The value of magnetic induction at zero time.
Dependencies
This parameter is used when the parameter Magnetization inductance parameterized by is set to . Magnetic flux density versus magnetic field strength characteristic with hysteresis
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Magnetization inductance field strength —
initial field strength of magnetising inductance
A/m
Details
The value of the magnetic field strength at zero time.
Dependencies
This parameter is used when the parameter Magnetization inductance parameterized by is set to . Magnetic flux density versus magnetic field strength characteristic with hysteresis
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Second winding burden inductance initial current —
initial load inductance current of the second winding
A
| MA
| kA
| mA
| nA
| pA
| uA
Details
Initial load inductance current of the second winding.
Dependencies
To use this parameter, select the checkbox Include burden, and for the parameter Burden type set the value to L
or Series RL
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Third winding burden inductance initial current —
initial load inductance current of the third winding
A
| MA
| kA
| mA
| nA
| pA
| uA
Details
Initial load inductance current of the third winding.
Dependencies
To use this parameters:
-
select the check box Include burden;
-
set the Burden type parameters to
L
orSeries RL
; -
set the Number of windings parameters to
Three
,Four
,Five
orSix
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Fourth winding burden inductance initial current —
initial load inductance current of the fourth winding
A
| MA
| kA
| mA
| nA
| pA
| uA
Details
Initial load inductance current of the fourth winding.
Dependencies
To use this parameters:
-
select the check box Include burden;
-
set the Burden type parameters to
L
orSeries RL
; -
set the Number of windings parameters to
Four
,Five
orSix
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Fifth winding burden inductance initial current —
initial load inductance current of the fifth winding
A
| MA
| kA
| mA
| nA
| pA
| uA
Details
Initial load inductance current of the fifth winding.
Dependencies
To use this parameters:
-
select the check box Include burden;
-
set the Burden type parameters to
L
orSeries RL
; -
set the Number of windings parameters to
Five
orSix
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Sixth winding burden inductance initial current —
initial load inductance current of the sixth winding
A
| MA
| kA
| mA
| nA
| pA
| uA
Details
Initial load inductance current of the sixth winding.
Dependencies
To use this parameters:
-
select the check box Include burden;
-
set the Burden type parameters to
L
orSeries RL
; -
set the Number of windings parameters to
Six
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
Parasitic
#
Combined leakage inductance parasitic parallel conductance —
parasitic parallel conductance of the total scattering inductance
S
| mS
| nS
| uS
| 1/Ohm
Details
This parameters is used to represent small parasitic effects in parallel to the aggregate scattering inductance. The small parallel conductance may be required for modelling some circuit topologies.
Dependencies
To use this parameter, set the parameter Winding parameterized by to the value of Combined primary and secondary values
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
First leakage inductance parasitic parallel conductance —
parasitic parallel conductance of the first winding scattering inductance
S
| mS
| nS
| uS
| 1/Ohm
Details
This parameter is used to represent small parasitic effects in parallel with the scattering inductance on the first winding. The small parallel conductance may be required for modelling some circuit topologies.
Dependencies
To use this parameter, set the Winding parameterized by parameters to Separate primary and secondary values
or set the Number of windings parameters to . Three
, Four
, Five
or Six
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Second leakage inductance parasitic parallel conductance —
parasitic parallel conductance of the second winding scattering inductance
S
| mS
| nS
| uS
| 1/Ohm
Details
This parameter is used to represent small parasitic effects parallel to the scattering inductance on the second winding.
Dependencies
To use this parameter, set the Winding parameterized by parameters to the value of Separate primary and secondary values
or set the Number of windings parameters to. Three
, Four
, Five
or Six
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Third leakage inductance parasitic parallel conductance —
parasitic parallel conductance of the third winding scattering inductance
S
| mS
| nS
| uS
| 1/Ohm
Details
This parameter is used to represent small parasitic effects in parallel to the scattering inductance on the third winding.
Dependencies
To use this parameter, set the parameter Number of windings to . Three
, Four
, Five
or Six
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Fourth leakage inductance parasitic parallel conductance —
parasitic parallel conductance of the fourth winding scattering inductance
S
| mS
| nS
| uS
| 1/Ohm
Details
This parameter is used to represent small parasitic effects parallel to the scattering inductance on the fourth winding.
Dependencies
To use this parameter, set the parameter Number of windings to . Four
, Five
or Six
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Fifth leakage inductance parasitic parallel conductance —
parasitic parallel conductance of the fifth winding scattering inductance
S
| mS
| nS
| uS
| 1/Ohm
Details
This parameter is used to represent small parasitic effects parallel to the fifth winding scattering inductance.
Dependencies
To use this parameter, set the parameters Number of windings to Five
or Six
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Sixth leakage inductance parasitic parallel conductance —
parasitic parallel conductance of the sixth winding scattering inductance
S
| mS
| nS
| uS
| 1/Ohm
Details
This parameter is used to represent small parasitic effects parallel to the scattering inductance on the sixth winding.
Dependencies
To use this parameter, set the parameters Number of windings to . Six
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Second winding burden inductance parasitic parallel conductance —
parasitic parallel conductance of the load inductance of the second winding
S
| mS
| nS
| uS
| 1/Ohm
Details
Parasitic parallel conductance of the load inductance of the second winding.
Dependencies
To use this parameters, tick the checkbox Include burden.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Third winding burden inductance parasitic parallel conductance —
parasitic parallel conductance of the load inductance of the third winding
S
| mS
| nS
| uS
| 1/Ohm
Details
Parasitic parallel conductance of the third winding load inductance.
Dependencies
To use this parameter, select the Include burden checkbox and set the Number of windings parameters to Three
, Four
, Five
or Six
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Fourth winding burden inductance parasitic parallel conductance —
parasitic parallel conductance of the fourth winding load inductance
S
| mS
| nS
| uS
| 1/Ohm
Details
Parasitic parallel conductance of the fourth winding load inductance.
Dependencies
To use this parameter, select the checkbox Include burden, and set the parameters Number of windings to a value of Four
, Five
or Six
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Fifth winding burden inductance parasitic parallel conductance —
parasitic parallel conductance of the fifth winding load inductance
S
| mS
| nS
| uS
| 1/Ohm
Details
Parasitic parallel conductance of the fifth winding load inductance.
Dependencies
To use this parameter, tick the checkbox Include burden, and for the parameter Number of windings set the value to Five
or Six
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |
#
Sixth winding burden inductance parasitic parallel conductance —
parasitic parallel conductance of the sixth winding load inductance
S
| mS
| nS
| uS
| 1/Ohm
Details
Parasitic parallel conductance of the load inductance of the sixth winding.
Dependencies
To use this parameter, select the checkbox Include burden, and set the parameters Number of windings to the value of Six
.
Units |
|
Default value |
|
Program usage name |
|
Evaluatable |
Yes |